MSD-EU TVD-LD — Low Duty Tunnel Ventilation Damper
MSD-EU TVD-LD — Low Duty Tunnel Ventilation Damper
MSD-EU TVD-LD is a low-duty, multi-blade metal damper developed for tunnel ventilation and smoke control systems. Its reinforced casing, double-skin aerofoil blades and external linkage mechanism support open/close operation and end-position feedback with the selected electric actuator.
- Single modules from 250 × 250 to 2800 × 2800 mm; larger openings use combined modules.
- 300 mm casing depth with Z275 galvanised steel or stainless steel options.
- Catalogue performance: 600°C integrity for 120 minutes and EN 1751 Class 4 closed-blade leakage.
Technical specifications
| Specification | Details |
|---|---|
| Damper construction | Opposed-blade action, double-skin aerofoil blades and external metal linkage arms |
| Casing and blade materials | Z275 galvanised steel; AISI 304, 316, 316L or 316Ti stainless steel options |
| Casing depth | 300 mm |
| Single-module dimensions | 250 × 250–2800 × 2800 mm; final module size depends on the selected drive configuration |
| Shaft and bearings | Ø25 mm AISI 304 shaft and bronze bushings |
| Casing sheet thickness | 2.0 / 2.5 / 3.0 mm |
| Double-skin blade sheet thickness | 1+1 / 1.2+1.2 / 1.5+1.5 mm |
Test and performance information
The following results are stated in the 2026 / Rev. 01 product catalogue.
| Test or standard | Catalogue result |
|---|---|
| EN 1366-10 fire test | Class E integrity maintained for 120 minutes under 600°C furnace exposure; Applus+ laboratory |
| EN 13501-4 classification | E600-S |
| EN 1751 closed-blade leakage | Class 4 at 1000–2000 Pa |
| Horizontal and vertical operation | 250°C for 1 hour |
| Thermal shock | Full open/close operation after −5°C to +250°C thermal shock |
| Mechanical endurance | 100,000 cycles |
The classification applies to the tested specimen size, installation position and drive configuration. Project applications must be based on the scope of the relevant test report.
Actuation and project selection
The standard arrangement uses a spring-return actuator. Electric 24 V, 120 V and 230 V, electro-hydraulic and pneumatic options are listed in the catalogue. Drive location may be inside or outside the airstream. Fail-safe behaviour, torque, thermal protection and position feedback are specified for the selected configuration.
With GGA326.1E, the catalogue specifies modules up to 1500 × 1500 mm. Other suitable actuator arrangements cover single modules up to 2800 × 2800 mm. Larger assemblies require a project-specific modular arrangement.
For selection, provide width × height, casing and blade materials, actuator type, supply voltage, mounting orientation, position indication and any thermal enclosure requirement.
Applications
Road and rail tunnels, metro and underground transport structures, ventilation shafts, smoke extraction ducts and high-temperature ventilation systems.
Frequently asked questions
What is MSD-EU TVD-LD used for?
It regulates airflow in tunnel ventilation systems and supports smoke control in tunnel and underground applications. Selection is based on the project requirements and the applicable test-report scope.
Does the 600°C test mean continuous operation at 600°C?
No. The catalogue states 120 minutes of integrity under 600°C furnace exposure. Its separate operating test is 250°C for 1 hour. These are different performance conditions.
Can the damper be supplied in stainless steel?
Yes. Alongside Z275 galvanised steel, the catalogue lists AISI 304, 316, 316L and 316Ti options for the casing and blades.
Downloads
Download the technical catalogue for dimensional drawings, actuator options, performance data and factory acceptance test information.
Opposed-blade tunnel ventilation damper for airflow regulation and smoke control in road, rail and metro tunnels.